Select a problem from the list below to see the possible causes and solutions.

Power Quality Troubleshooting Chart

SYMPTOMPower Event Possibilities:
--note--Events are arranged in order of statistical probability
Circuit Breaker-- Tripping
(current measured)
Voltage Sag
Voltage Distortion
Neutral Current*
*see TRMS Measuring Equipment
Circuit Breaker -- Tripping
(Nuisance)
Voltage Distortion
Neutral Current
Computer-- Hard Disk CrashingImpulse
Outage
Computer-- Locking UpImpulse
Repetitive Disturbance
Computer-- Low Voltage Inhibit ActivatingOutage
Voltage Sag
Computer-- Communication Parity ErrorsImpulse
Neutral-Ground Voltage
Repetitive Disturbance
Computer-- Process InterruptionsImpulse
Outage
Voltage Sag
Computers-- Re-se tting/Requiring Frequent Re-BootImpulse
Neutral-Ground Voltage
Outage
Voltage Sag
Computer-- Software ErrorsImpulse
Voltage Sag
Repetitive Disturbance
Computer/UPS-- Dead BatteriesOutage
Impulse (charging system failure)
Control System Speed  or Settings DriftingImpulse
Repetitive Disturbance
Electronic-- Circuit Board FailuresImpulse
Repetitive Disturbance
Electronic-- Component FailuresImpulse
Repetitive Disturbance
Electronic-- Overheating ComponentsVoltage Distortion
Repetitive Disturbance
Equipment-- Erratic OperationNeutral-Ground Voltage
Impulse
Repetitive Disturbance
Lack of Phase SynchronizationVoltage Distortion
Measurement ErrorsImpulse
Repetitive Disturbance
Motor FailuresVoltage Distortion
Impulse
Neutral Current 
(Excessive)
Non-Sinusoidal Phase Current
Neutral Current
Noise (Audible)Repetitive Disturbance
Impulse
Overheating (or hot) TransformersNon-Sinusoidal Phase Current
Repetitive Disturbance
Overheating (or hot)  Wiring & ConduitNon-Sinusoidal Phase Current
Repetitive Disturbance
Power Supply FailuresImpulse
Repetitive Disturbance
Outage
Surge Suppressor FailuresRepetitive Disturbance
Telephone Dropped CallsImpulse
Neutral-Ground Voltage
Outage
Voltage Sag
Repetitive Disturbance


 



IMPULSE

Probable Cause:
--note--not listed in any particular order
Possible Solutions:
1. SCR-Controlled Loads1. Repair Replace Faulty Wiring
2. Variable Speed Drives2. Repair/Replace Faulty Breakers
3. Faulty Wiring and/or Circuit
Breakers
3. Add Snubbers to Contacts and Relays
4. Load Startup or Disconnect4. Surge Suppression (All)
5. Power Factor Correction5. Move Source of Disturbanceor Load
6. Lightning 6. Surge Suppression
7. Photocopiers/Laser Printers 7. Surge Suppression






REPETITIVE DISTURBANCE

Probable Cause:
--note--not listed in any particular order
Possible Solutions:
1. SCR-Controlled Drives1. Surge Suppression
2. Variable speed Drives2. Move Source of Disturbance or Load
3. UPS/Motor Generator Instability3. Isolate Source (with Transformer or Surge Suppressor)
4. Light Dimmers4. Surge Suppressors
5. Arc Welders5. Surge Suppressors



 



NEUTRAL-GROUND VOLTAGE

Probable Cause:
--note--not listed in any particular order
Possible Solutions:
1. Faulty Wiring and/or Circuit
Breakers
1. Repair/ Replace Faulty Wiring
2. Load Startup or Disconnect2. Correct Faults to Ground
3. Loose or Missing N-G Bond3. Correct Wiring Deficiencies
4. Excessive Ground Current4. Correct Wiring
5. Faults to Ground5. Replace Equipment
6. Excessive Neutral Current6. Harmonics Mitigation Equipment






OUTAGE

Probable Cause:
--note--not listed in any particular order
Possible Solutions:
1. Faulty Wiring and/or Circuit Breakers1. Repair/Replace Faulty Breakers
2. Utility Power Fault2. Surge Suppression  (for protection on re-start)
3. Alternative Power Source Failure3. Install UPS
4. Local Circuit Breaker Trip4. Install Alternate Power Source






VOLTAGE SAG

Probable Cause:
--note--not listed in any particular order
Possible Solutions:
1. Faulty Wiring and/or Circuit Breakers1. Repair/Replace Faulty Wiring
2. Load Startup or Disconnect2. Repair/Replace Faulty Breakers
3. Utility Power Fault3. Surge Suppression 
(for protection on power return)
4. Faults and Short4. Install UPS
 5. Install Alternate Power Source






VOLTAGE DISTORTION

Probable Cause:
--note--not listed in any particular order
Possible Solutions:
1. SCR Controlled Loads1. Repair/Replace Faulty Wiring
2. Variable Speed Drives2. Surge Suppression (Some noise protection)
3. UPS/Motor Generator Instability3. Reduce Impedance of Power  Source
4. Switching Mode Power Supplies4. Use RMS not Peak Sensing Circuitry to Control Conditioning
5. High Impedance Sources5. Isolate Sources
6. High Impedance Electrical
Wiring
6. Repair/Replace Wiring






NON-SINUSOIDAL PHASE CURRENT

Probable Cause:
--note--not listed in any particular order
Possible Solutions:
1. Variable Speed Drives1. Surge Suppression  (Isolation of distorting loads)
2. UPS/Motor Generator Instability2. Repair Power Source
3. Computers3. Decrease Non-sinusoidal Load
4. Electronic Ballasts4. Replace Ballasts






NEUTRAL CURRENT
Probable Cause:
--note--not listed in any particular order
Possible Solutions:
1. SCR-Controlled Loads1. Add Power Treatment Devices (Capacitance)
2. Phase-Neutral Powered Rectified Loads2. Increase Gage of Wiring
3. Phase Imbalance3. Balance Phase
 4. Harmonically Balance Loads


 


PHONE
 (678) 546-6780
FAX
(678) 546-6782

Technical Support
tech@tvss.net

Stedi-Power, Inc.
5044 B U Bowman Drive,
Suite 102
Buford GA 30518

General Inquiries
help@tvss.net

 

           



Stedi-Power, Inc
5044 B U Bowman Drive #102
Buford, Georgia 30518

PHONE: (678) 546-6780

Last Updated: 07 Jun 2004
©1997-2004 Stedi-Power, Inc.
All trademarks are the property of their respective owners
All other rights reserved.